Erik; What "terminal box" are you referring to. We recommend using PVC
conduit in the ground. 1 inch works well. Buy individual wires number 6
THHN/THWN and number 8 THHN/THWN.
If you bring the conduit up just to the side of the spa, you can make a
transition to Flex Carlon liquid tight 3/4 inch with a ridged coupling and a
reducer bushing. You do not need a box outside the spa.
Pull the four wires up and out of the solid PVC first, then put the coupling
and reducer bushing over the wires. Then put the wires in the flex before
attaching it to the solid PVC. Leave a whip of 8 to 10 feet with the wires
hanging out about 8 inches on the end of the flex where the flex connector
goes.
The GFCI box must be put no closer than 5 feet of the spa and no farther than
50 feet, line of site to the spa. No one should be able to reach the GFCI
while in the spa.
The Spa is scheduled to leave this week. I have not been able to get an
exact time. We will be talking with the delivery guy either tomorrow or the
next day.
Jim
"Erik W. Selberg" wrote:
> Hey Jim,
>
> Dug the trench for the electrical yesterday. I'm a bit concerned about
> the intended placement of the terminal box as to whether or not it's
> too close to the hot tub.
>
> Here's a rough diagram of my back yard:
>
> ______________________________
> |
> |
> | __________
> | |####### |
> | |####### |
> | x|# spa # |
> | !|####### |
> | !|####### |
> | !| |
> | !| |
> | !| |
> |_!| |
>
> The N and W sides have a fenceline, and there's a cement patio where
> the spa will go. I've dug the trench for the electrical along the
> patio, with the terminal box where the whip will come out looking to
> be mid-way on the side of the spa (I assume the lounge side which is
> where the electrical is). However, in thinking about this, I'm
> concerned that there won't be enough space between the terminal box
> (which would presumably stick up some 18") and the spa, (there'd
> probably be only a few inches); or it could be in the way of getting
> at the access panel there.
>
> Is this a valid concern? Or is this a good placement for the terminal
> box? Presumably, I could put the box lower or towards either corner of
> the tub with little difficulty as well.
>
> BTW, when does the truck leave? My buddies who helped me did the
> trench are anxious for their payback. :)
>
> Thanks,
> -e
>
> --
> Erik Selberg
> "I get by with a little help selberg@cs.washington.edu
> from my friends." http://www.cs.washington.edu/homes/selberg